A pipe schedule is a standardized wall-thickness designation for a nominal pipe size, not a pressure rating and not a material grade. ASME B36.10M standardizes dimensions of welded and seamless wrought steel pipe. ASME B36.19M does the same for welded and seamless wrought stainless steel pipe. The same schedule number does not mean one wall thickness at every size.
Read the schedule against one nominal size
NPS and DN identify the nominal size. For pipe NPS 12 (DN 300) and smaller, the outside diameter is numerically larger than the size number. That is the pipe convention. Tube uses a different size convention, so a tube size cannot be substituted for a pipe schedule.
The higher schedule number means a thicker wall only when the nominal size stays the same. NPS 2 Schedule 40 and NPS 4 Schedule 40 are different thicknesses. A chart that omits the nominal size cannot be used to order pipe.
The old explanation that schedule equals 1,000 times pressure divided by stress is history, not an ordering rule. Modern allowable stresses have changed. Use the current design code and the current pipe-dimension standard. Confirm the edition before treating a table as mandatory; this page does not reproduce a controlled dimension table.
The S schedules are a stainless-steel series
ASME B36.19M uses an S suffix, as in 5S, 10S, 40S and 80S, to distinguish its stainless-steel pipe series from ASME B36.10M pipe. The ASME catalogue states that the suffix is there for that distinction. It also states that some listed walls are not the same as B36.10M: NPS 14 through 22 of Schedule 10S, NPS 12 of Schedule 40S, and NPS 10 and 12 of Schedule 80S.
Because those identities differ, an order for stainless pipe needs both the grade and the S schedule. "4-inch Schedule 10" is not a complete substitute for "4-inch Schedule 10S" when the stainless series is required. B36.10M thicknesses can also be produced in stainless material, so the inquiry must say which standard governs.
Schedule 5S and 10S are thin-wall series used where the design allows that wall. They are not a sanitary certification, and they are not available as a promise for every grade and length.
STD, XS and XXS are not automatic aliases
Standard (STD), extra-strong (XS) and double-extra-strong (XXS) are older wall designations. They line up with some schedule numbers at some sizes, and they diverge at others. In particular, do not assume STD and Schedule 40 are identical above NPS 10. Specify the designation that appears in the design document, then check it in the current ASME table for that exact NPS.
Schedule 160 and XXS are thick-wall designations, not a claim that every mill can produce them in every grade. If the design needs a wall between two standard schedules, that is a specified millimetre or inch thickness, not a new schedule name.
Pressure rating is calculated after the wall is known
Wall thickness is an input to the pressure design. It is not the rating itself. The design calculation has to use the code named for the piping system, the allowable stress of the actual material at the design temperature, the outside diameter, corrosion or mechanical allowance, and the joint quality factor for welded pipe.
ASME B31.3 is one process-piping code that uses those inputs. It does not make Schedule 80 a fixed multiple of Schedule 40. A published working-pressure number for one grade, one size and one temperature cannot be copied to another combination. Welded pipe and seamless pipe of the same nominal schedule can also have different joint factors under that code.
Temperature changes the result. Allowable stress is read from the code's stress tables for the grade and temperature, not from a room-temperature brochure. If the operating temperature is still unknown, the schedule is not ready to freeze.
Checks before the schedule is released
- Design pressure, design temperature and the governing piping code.
- Material grade and product form, including welded or seamless.
- NPS or DN, outside diameter and the schedule or specified wall.
- For stainless pipe, whether B36.19M S schedules apply.
- Corrosion allowance, joint quality factor and the current standard edition.
A published example of a specified schedule is 5-inch Schedule 40 galvanized pipe. Where the design calls for seamless carbon-steel pipe rather than a welded schedule, start from seamless carbon steel pipe and state the schedule on the inquiry. The schedule number alone is not the product.